Niedostępne

Generator AC Kogeneracja

Generator AC Kogeneracja
Magazyn #:
RG8458
USED BIOMASS PLANT BUILT BY MW POWER (WARTSILA) BASED ON THE BP5 CEX MODEL. PLANT IS CONFIGURED TO OPERATE IN FULLY CONDENSING MODE OR WITH STEAM EXTRACTION. PLANT CONTAINS A BIOGRATE WITH ROTATING COMBUSTION TECHNOLOGY, A WATER TUBE BOILER, SNCR FOR LOW-NOX COMBUSTION, AN ABILITY TO SEPARATE BOTTOM ASH AND FLY ASH IN TWO SEPARATE CONTAINERS AND IS FULLY AUTOMATED TO ENABLE UNMANNED OPERATION. PLANT IS REPORTEDLY CAPABLE OF PRODUCING 4.7 MW OF ELECTRICITY WITH A FUEL CONSUMPTION OF 20.8 MW OF FUEL (30M3/H). IN CHP MODE PLANT CAN REPORTEDLY PRODUCE UP TO 3.1 MW OF ELECTRICITY AND 10TE/H OF PROCESS STEAM. PROCESS VALUES: - STEAM PRESSURE AT TURBINE INLET 62 BARA - STEAM TEMPERATURE AT TURBINE INLET 480 DEGREES CELSIUS - STEAM FLOW 21.7 TE/H - TURBINE EXTRACTION PRESSURE 10 BARA - TEMPERATURE FEED WATER TANK 105 DEGREES CELSIUS (130 DEGREES CELCIUS WHEN BURNING SPENT GRAIN) - FLUE GAS TEMPERATURE AFTER BOILER APPROXIMATELY 160 DEGREES CELSIUS - AUXILLIARY ELECTRICITY CONSUMPTION 722 KW EQUIPMENT LIST AND SPECIFICATIONS AVAILABLE ON DEMAND.